Back to results
Water SA Manuscript

Faecal coliforms, faecal enterococci, Salmonella Typhi and Acanthamoeba spp. UV inactivation in three different biological effluents

Published: 2008
Report No: 2 183,00
Authors: Beltrán NA, Jiménez BE

Abstract

Efficiency of UV-light to inactivate microbial indicators, Salmonella Typhi and Acanthamoeba spp. was studied in three different biological secondary effluents. Even though effluents differed in terms of their total suspended solids content, transmittance and particle size distribution, the UV-light dose required to fulfil WHO agricultural water reuse criteria was the same (30 mW·s/cm2), because the particle content with sizes >40 µm was similar and very small. Using this dosage, 3 log of Salmonella Typhi and faecal enterococci were also inactivated. To avoid faecal coliform and Salmonella Typhi photoreactivation, the UV dose had to be doubled and in the process 2.5 log of Acanthamoeba spp. were also inactivated. This is interesting because its presence in wastewater, pathogenicity and resistance to conventional disinfection processes has been reported in the literature.

Authors

BN
Beltrán NA
JB
Jiménez BE

Categories

Access Report

Free download · PDF format

Related Research