Back to results
Water SA Manuscript
TECHNICAL NOTE: Reduction of Langelier index of cooling water by electrolytic treatment with stainless steel electrode
Published: 2012
Report No: 2 769,00
Authors: Rungvavmanee R, Phalakornkule C
Abstract
The efficiency of electrolytic treatment in reducing the Langelier saturation index (LSI) of the cooling water from a cooling tower of a textile industry was investigated. Sacrificial anodes were employed which prevent obnoxious chlorine generation. A series of batch experiments using stainless steel electrodes were conducted with 4 different current densities (5, 7, 10 and 15 A/m2) and 6 different electrolysis times (20, 30, 40, 50, 60 and 70 min). The use of 7 A/m 2 for 50 min electrolysis time yielded a satisfactory efficiency in reducing the LSI index from 2.57 to zero, indicating that the treated water was of sufficient quality to be reused in the cooling process.
Authors
RR
Rungvavmanee R
PC
Phalakornkule C
Access Report
Free download · PDF format
Related Research
Mapping transition pathways for water graduates to support water sector innovation in South Africa
01 Mar 2023
I don't understand what you're asking me... Interviewees' understanding of questionnaires relating to safe and reliable water and sanitation services
01 Jul 2021
Pipe liner technology for bulk water pipeline rehabilitation - A strategic framework for South African water boards
01 Aug 2026
Integrated Urban Water Modelling for South African Water Services
01 Oct 2025